Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases

Karel Lambert (UGent) and Bart Merci (UGent)
(2014) FIRE TECHNOLOGY. 50(6). p.1517-1534
Author
Organization
Abstract
During fire service interventions, positive pressure ventilation (PPV) systems with mobile fans are often used to try and make (or keep) a staircase smoke free and to remove smoke from the fire rooms. The positioning (distance from the door opening) and inclination angle of the fan determine the effect of the PPV fans in the staircase. In the present paper results are discussed of an experimental study, performed at full-scale. Based on different sets of cold experiments, the impact is quantified of: the distance between the fan and the door; the inclination angle of a single fan; and the use of multiple fans. The closer the single fan is put to the door opening, the more effective the PPV becomes. Obviously, there is a trade-off with effectiveness of the fire service intervention, since the fan must not block the door opening. With respect to inclination, it is best to apply an inclination angle of 75A degrees (i.e., an upward tilting of the fan axis by 15A degrees, which is the maximum value tested) for ventilation at ground level with the fan tested. This ensures safety in the case of fire at ground level due to full coverage of the entry door opening, while only a relatively limited loss in PPV effectiveness is observed compared to a horizontal fan (in some cases, the PPV effectiveness is even higher with inclined fan). When the fire room is at a higher floor, an inclination angle of 90A degrees (i.e. horizontal fan axis) can generate a higher average flow velocity, depending on the staircase configuration inside the building. If two fans are used, V-shape positioning is shown to be more effective than a set-up in series or in parallel. A V-shape with inner angle of 60A degrees between the fan axes is more effective than an angle of 90A degrees. If three fans are available, still higher average flow velocities are measured. Positioning two fans outside in V-shape and one fan inside at the bottom of the staircase is more effective than putting the three fans outside, On the other hand, the latter set-up may be required for firefighting tactics.
Keywords
Fire service intervention, PPV, Full-scale experiments, Positive pressure ventilation

Downloads

  • FT Lambert 130903.pdf
    • full text
    • |
    • open access
    • |
    • PDF
    • |
    • 912.48 KB

Citation

Please use this url to cite or link to this publication:

MLA
Lambert, Karel, and Bart Merci. “Experimental Study on the Use of Positive Pressure Ventilation for Fire Service Interventions in Buildings with Staircases.” FIRE TECHNOLOGY, vol. 50, no. 6, 2014, pp. 1517–34, doi:10.1007/s10694-013-0359-0.
APA
Lambert, K., & Merci, B. (2014). Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases. FIRE TECHNOLOGY, 50(6), 1517–1534. https://doi.org/10.1007/s10694-013-0359-0
Chicago author-date
Lambert, Karel, and Bart Merci. 2014. “Experimental Study on the Use of Positive Pressure Ventilation for Fire Service Interventions in Buildings with Staircases.” FIRE TECHNOLOGY 50 (6): 1517–34. https://doi.org/10.1007/s10694-013-0359-0.
Chicago author-date (all authors)
Lambert, Karel, and Bart Merci. 2014. “Experimental Study on the Use of Positive Pressure Ventilation for Fire Service Interventions in Buildings with Staircases.” FIRE TECHNOLOGY 50 (6): 1517–1534. doi:10.1007/s10694-013-0359-0.
Vancouver
1.
Lambert K, Merci B. Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases. FIRE TECHNOLOGY. 2014;50(6):1517–34.
IEEE
[1]
K. Lambert and B. Merci, “Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases,” FIRE TECHNOLOGY, vol. 50, no. 6, pp. 1517–1534, 2014.
@article{5992951,
  abstract     = {{During fire service interventions, positive pressure ventilation (PPV) systems with mobile fans are often used to try and make (or keep) a staircase smoke free and to remove smoke from the fire rooms. The positioning (distance from the door opening) and inclination angle of the fan determine the effect of the PPV fans in the staircase. In the present paper results are discussed of an experimental study, performed at full-scale. Based on different sets of cold experiments, the impact is quantified of: the distance between the fan and the door; the inclination angle of a single fan; and the use of multiple fans. The closer the single fan is put to the door opening, the more effective the PPV becomes. Obviously, there is a trade-off with effectiveness of the fire service intervention, since the fan must not block the door opening. With respect to inclination, it is best to apply an inclination angle of 75A degrees (i.e., an upward tilting of the fan axis by 15A degrees, which is the maximum value tested) for ventilation at ground level with the fan tested. This ensures safety in the case of fire at ground level due to full coverage of the entry door opening, while only a relatively limited loss in PPV effectiveness is observed compared to a horizontal fan (in some cases, the PPV effectiveness is even higher with inclined fan). When the fire room is at a higher floor, an inclination angle of 90A degrees (i.e. horizontal fan axis) can generate a higher average flow velocity, depending on the staircase configuration inside the building. If two fans are used, V-shape positioning is shown to be more effective than a set-up in series or in parallel. A V-shape with inner angle of 60A degrees between the fan axes is more effective than an angle of 90A degrees. If three fans are available, still higher average flow velocities are measured. Positioning two fans outside in V-shape and one fan inside at the bottom of the staircase is more effective than putting the three fans outside, On the other hand, the latter set-up may be required for firefighting tactics.}},
  author       = {{Lambert, Karel and Merci, Bart}},
  issn         = {{0015-2684}},
  journal      = {{FIRE TECHNOLOGY}},
  keywords     = {{Fire service intervention,PPV,Full-scale experiments,Positive pressure ventilation}},
  language     = {{eng}},
  number       = {{6}},
  pages        = {{1517--1534}},
  title        = {{Experimental study on the use of positive pressure ventilation for fire service interventions in buildings with staircases}},
  url          = {{http://doi.org/10.1007/s10694-013-0359-0}},
  volume       = {{50}},
  year         = {{2014}},
}

Altmetric
View in Altmetric
Web of Science
Times cited: