Advanced search
1 file | 989.80 KB

Analysis of the neutral conductor current in a three-phase supplied network with nonlinear single-phase loads

Author
Organization
Abstract
This paper describes. what factors (i.e., load and supply) have an important effect on the neutral conductor current. It is shown that an asymmetry up to 10degrees or an unbalance of 10% in the power supply has only a minor effect on the rms value of the neutral conductor current. An unbalance in load conditions increases the neutral conductor current. Harmonics in the power supply voltage highly affect the rms value of the neutral conductor current.
Keywords
power quality, neutral conductor, nonlinear loads, harmonic distortion, current measurement

Downloads

  • (...).pdf
    • full text
    • |
    • UGent only
    • |
    • PDF
    • |
    • 989.80 KB

Citation

Please use this url to cite or link to this publication:

Chicago
Desmet, Jan, Isabel Sweertvaegher, Greet Vanalme, Kurt Stockman, and Ronny Belmans. 2003. “Analysis of the Neutral Conductor Current in a Three-phase Supplied Network with Nonlinear Single-phase Loads.” Ieee Transactions on Industry Applications 39 (3): 587–593.
APA
Desmet, Jan, Sweertvaegher, I., Vanalme, G., Stockman, K., & Belmans, R. (2003). Analysis of the neutral conductor current in a three-phase supplied network with nonlinear single-phase loads. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 39(3), 587–593. Presented at the IEEE International Electric Machines and Drives Conference.
Vancouver
1.
Desmet J, Sweertvaegher I, Vanalme G, Stockman K, Belmans R. Analysis of the neutral conductor current in a three-phase supplied network with nonlinear single-phase loads. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS. 2003;39(3):587–93.
MLA
Desmet, Jan, Isabel Sweertvaegher, Greet Vanalme, et al. “Analysis of the Neutral Conductor Current in a Three-phase Supplied Network with Nonlinear Single-phase Loads.” IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS 39.3 (2003): 587–593. Print.
@article{3054167,
  abstract     = {This paper describes. what factors (i.e., load and supply) have an important effect on the neutral conductor current. It is shown that an asymmetry up to 10degrees or an unbalance of 10\% in the power supply has only a minor effect on the rms value of the neutral conductor current. An unbalance in load conditions increases the neutral conductor current. Harmonics in the power supply voltage highly affect the rms value of the neutral conductor current.},
  author       = {Desmet, Jan and Sweertvaegher, Isabel and Vanalme, Greet and Stockman, Kurt and Belmans, Ronny},
  issn         = {0093-9994},
  journal      = {IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS},
  keyword      = {power quality,neutral conductor,nonlinear loads,harmonic distortion,current measurement},
  language     = {eng},
  location     = {Cambridge, MA, USA},
  number       = {3},
  pages        = {587--593},
  title        = {Analysis of the neutral conductor current in a three-phase supplied network with nonlinear single-phase loads},
  url          = {http://dx.doi.org/10.1109/TIA.2003.810638},
  volume       = {39},
  year         = {2003},
}

Altmetric
View in Altmetric
Web of Science
Times cited: