Influence of contact resistance on shielding efficiency of shielding gutters for HV cables

Author
Organization
Abstract
Shielding of buried three phase high voltage cables can be done by placing the cables in conducting ferromagnetic U-shaped gutters covered by plates. In case of a perfect electrical contact between adjacent gutters and between adjacent cover plates, the induced currents in the shield efficiently reduce the field generated in the vicinity of the cables. However, as a perfect contact cannot be guaranteed, it is useful to quantify the effect of a bad electrical contact on the shielding performance. From 2D FEM, 3D FEM and experiments, it is observed that a bad contact does not influence significantly the shielding if the axial length of the plates is relatively long compared to their other dimensions.
Keywords
shielding efficiency, contact resistance, shielding gutters, buried three phase high voltage cable shielding, cover plates, ferromagnetic U-shaped gutters, perfect electrical contact, 2D FEM, 3D FEM, electrical contacts, finite element analysis, cable shielding, power cables, HV cables

Downloads

  • CEFC2010 HVcables KorogluDigest Rev.pdf
    • full text
    • |
    • open access
    • |
    • PDF
    • |
    • 204.70 KB

Citation

Please use this url to cite or link to this publication:

Chicago
Koroglu, Selim, Peter Sergeant, Ruth Sabariego, Vuong Dang Quoc, and Marc De Wulf. 2010. “Influence of Contact Resistance on Shielding Efficiency of Shielding Gutters for HV Cables.” In Electromagnetic Field Computation, 14th Biennial IEEE Conference, Proceedings. Piscataway, NJ, USA: IEEE.
APA
Koroglu, S., Sergeant, P., Sabariego, R., Dang Quoc, V., & De Wulf, M. (2010). Influence of contact resistance on shielding efficiency of shielding gutters for HV cables. Electromagnetic Field Computation, 14th Biennial IEEE Conference, Proceedings. Presented at the 14th Biennial IEEE Conference on Electromagnetic Field Computation (CEFC 2010), Piscataway, NJ, USA: IEEE.
Vancouver
1.
Koroglu S, Sergeant P, Sabariego R, Dang Quoc V, De Wulf M. Influence of contact resistance on shielding efficiency of shielding gutters for HV cables. Electromagnetic Field Computation, 14th Biennial IEEE Conference, Proceedings. Piscataway, NJ, USA: IEEE; 2010.
MLA
Koroglu, Selim et al. “Influence of Contact Resistance on Shielding Efficiency of Shielding Gutters for HV Cables.” Electromagnetic Field Computation, 14th Biennial IEEE Conference, Proceedings. Piscataway, NJ, USA: IEEE, 2010. Print.
@inproceedings{1023546,
  abstract     = {Shielding of buried three phase high voltage cables can be done by placing the cables in conducting ferromagnetic U-shaped gutters covered by plates. In case of a perfect electrical contact between adjacent gutters and between adjacent cover plates, the induced currents in the shield efficiently reduce the field generated in the vicinity of the cables. However, as a perfect contact cannot be guaranteed, it is useful to quantify the effect of a bad electrical contact on the shielding performance. From 2D FEM, 3D FEM and experiments, it is observed that a bad contact does not influence significantly the shielding if the axial length of the plates is relatively long compared to their other dimensions.},
  author       = {Koroglu, Selim and Sergeant, Peter and Sabariego, Ruth and Dang Quoc, Vuong and De Wulf, Marc},
  booktitle    = {Electromagnetic Field Computation, 14th Biennial IEEE Conference, Proceedings},
  isbn         = {9781424470594},
  keywords     = {shielding efficiency,contact resistance,shielding gutters,buried three phase high voltage cable shielding,cover plates,ferromagnetic U-shaped gutters,perfect electrical contact,2D FEM,3D FEM,electrical contacts,finite element analysis,cable shielding,power cables,HV cables},
  language     = {eng},
  location     = {Chicago, IL, USA},
  pages        = {1},
  publisher    = {IEEE},
  title        = {Influence of contact resistance on shielding efficiency of shielding gutters for HV cables},
  url          = {http://dx.doi.org/10.1109/CEFC.2010.5481447},